Section 7
Operating procedures
7.1.2
7.1.2.1
7.1.2.2
7.1.3
7.1.3.1
64
The internal event list is not updated dynamically. To update the
list, leave the Internal events menu and then select it again.
Measured and calculated values
All values show the momentary measurement value and some include demand
values calculated from a set period.
Measured values
Measured values can be accessed through the LHMI.
Using the local HMI for monitoring
If the LHMI displays --- instead of a measured float value, it
means that the value is invalid and out of range
1.
Select Main menu/Measurements to monitor measured and calculated
values.
The list of IED's basic measurements is shown.
2.
Scroll the view with
Recorded data
The IED is provided with intelligent and flexible functionality that collects
different kinds of data. The recorded data gives substantial information for post
fault analysis.
•
Disturbance records
•
Events
Creating disturbance recordings
Normally disturbance recordings are triggered by the IED applications but the
recording can also be triggered manually.
Set the DRPRDRE Operation to On via LHMI or PCM600 and at
least one channel has to be connected. To make the setting, select
Main menu/Settings/IED Settings and then Monitoring/
Disturbance report/DisturbanceReport/DRPRDRE:1.
and
.
1MRK 500 128-UEN B
GUID-4C43C62F-D641-4880-8067-B9D9C8EE25BA v7
AMU0600431 v6
AMU0600432 v7
GUID-1E9CFEC1-6245-4612-B637-821951B95D60 v7
GUID-B0CE46C1-1219-4BA2-9627-E53FC0413409 v5
650 series 2.2 IEC
Operation manual