Indication Messages; Internal Faults - ABB Relion 650 Series Operation Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 8
Troubleshooting
8.2
8.2.1
78
Headline
Time diff: IED vs Sampled value
Frequency diff: IED vs Sampled value
Invalid phase angle reference
GOOSE is configured on a disabled port
LDCM not running the application image
LDCM version is not accepted

Indication messages

Internal faults

When the Ready LED indicates an internal fault by flashing, the message
associated with the fault is found in the internal event list in the LHMI menu Main
menu/Diagnostics/Internal events. The message includes the date, time,
description and signal state for the fault. The internal event list is not updated
dynamically. The list is updated by leaving the Internal events menu and then
selecting it again. The current status of the internal fault signals can also be
checked via the LHMI in Main menu/Diagnostics/IED status.
Different actions are taken depending on the severity of the fault. If the fault is
found to be permanent, the IED stays in internal fault mode. The IED continues to
perform internal tests during the fault situation.
When a fault appears, the fault indication message is to be recorded and stated
when requesting support or service.
1MRK 500 128-UEN B
Explanation
<Access Point><Hardware Module
Identifier><svID>
Where the Hardware Module Identifier is the
same as given in PCM600, e.g. AP1: MU1_9201
svID: <ABB_MU0101>
<Access Point><Hardware Module
Identifier><svID>
Where the Hardware Module Identifier is the
same as given in PCM600, e.g. AP1: MU1_9201
svID: <ABB_MU0101>
PhaseAngleRef corresponds to an
The selected
analog channel that is not configured. Please
configure a valid reference channel.
At least one of the access points configured for
GOOSE is disabled. The port can be disabled
either through changing the access point
operation to off or by unchecking the GOOSE
protocol from the access point in the Ethernet
configuration in PCM600 or LHMI.
Please enable GOOSE on access points:
AP_FRONT, AP_1
<slot number> is running the factory image
instead of the application image. The factory
image is older and does not contain the latest
updates and fixes.
Please reboot the IED. If the problem persists
update the LDCM firmware or replace the board.
<device name> firmware version <version
string> is not accepted. The minimum accepted
version is <version string>.
Please update the LDCM firmware or replace the
board.
GUID-2ACAE73F-9CDD-4C33-AFED-6BACC8990F37 v7
650 series 2.2 IEC
Operation manual