Section 4
Overview
4.4
36
communication between the IEDs, is only enabled by the IEC 61850-8-1
communication protocol (GOOSE) and as Network Variables on LON.
The serial communication follows the EIA-485 standard and is intended to be used
in multi-point communication.
Disturbance files are accessed using the IEC 61850, IEC 60870-5-103, DNP, SPA,
LON or FTP protocols. The disturbances are in COMTRADE format. The IED can
send binary signals to other IEDs (so called horizontal communication) using the
IEC 61850-8-1 GOOSE (Generic Object Oriented Substation Event) profile or
through LON network variables. Binary GOOSE messaging can, for example, be
employed for protection and interlocking-based protection schemes.
The IED meets the GOOSE performance requirements for tripping applications in
transmission substations, as defined by the IEC 61850 standard. Further, the IED
supports the sending and receiving of analog values using GOOSE messaging.
Analog GOOSE messaging enables fast transfer of analog measurement values
over the station bus.
The IED interoperates with other IEC 61850 compliant IEDs, tools and systems
and simultaneously reports events to eight different clients on the IEC 61850
station bus. For a system using DNP3 over TCP/IP, events can be sent to four
different masters. For systems using IEC 60870-5-103 IED can be connected to
one master in a station bus with star-topology.
The IED has a number of communication ports which support different protocols:
Communication media
Ethernet (fiber-optic multimode LC connector,
that is 100BASE-FX)
Optical Serial port (glass with ST connector or
plastic with HFBR snap-in connector)
Optical LON port (glass with ST connector or
plastic with HFBR snap-in connector)
RS485
The IED supports IRIG-B, PPS, SNTP, PTP or Binary time synchronization
methods with a time-stamping resolution of 1 ms or better. Alternative time
synchronization methods are LON, SPA, DNP or IED 60870-5-103.

PCM600 tool

Protection and Control IED Manager PCM600 offers all the necessary functionality
to work throughout all stages of the IED life cycle.
1MRK 500 128-UEN B
Protocols supported
IEC 61850, FTP, PTP, HSR, PRP, SNTP
IEC 60870-5-103, DNP3, SPA
LON
IEC 60870-5-103, DNP3
AMU0600443 v11
650 series 2.2 IEC
Operation manual