Section 7
Operating procedures
7.4
7.4.1
7.4.1.1
70

Changing the IED functionality

Defining the setting group

Do not switch off the auxiliary power supply to the IED before
changes, for example, setting parameter or local/remote control
state changes are saved.
Do not switch off the auxiliary power supply to the IED before
changes. For example, when setting parameter changes are saved.

Activating a setting group

IED settings are planned in advance for different operation conditions by
calculating setting values to different setting groups. The active setting group can
be changed manually from the menu or by the PCM600 tool.
1.
Select Main menu/Settings/Active setting group/SETGRPS:1 and press
.
GUID-9BC3D595-CF08-42AF-B74E-0D3970A552DB V1 EN-US
Figure 44:
Active setting group
2.
Select the setting group with
3.
Press
to confirm the selection or
4.
Commit the settings.
GUID-A9853F1B-78ED-4AEF-AAE2-C27FF3DAE408 v3
IEC13000235-1-en.vsd
or
.
to cancel.
1MRK 500 128-UEN B
AMU0600439 v8
650 series 2.2 IEC
Operation manual