Authorization - ABB Relion 650 Series Operation Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 500 128-UEN B
4.2
650 series 2.2 IEC
Operation manual
GUID-40BD0177-1CB8-48D6-B149-D25BD109C78F V1 EN-US
Figure 13:
Example of a single-line diagram

Authorization

User roles with different user rights are predefined in the IED. It is recommended
to use user defined users instead of the predefined built-in users.
The IED users can be created, deleted and edited only with PCM600. One user can
belong to one or several user roles. By default, the users in Table
the IED, and when creating new users, the predefined roles from Table
used.
At delivery, the IED user has full access as SuperUser until users
are created with PCM600.
Table 10:
Default users
User name
User rights
SuperUser
Full rights, only presented in LHMI. LHMI is logged on by default until other users
are defined
Guest
Only read rights, only presented in LHMI. LHMI is logged on by default when
other users are defined (same as VIEWER)
Administrator
Full rights. Password: Administrator. This user has to be used when reading out
disturbances with third party FTP-client.
IEC13000244-1-en.vsd
GUID-981A881D-9229-45E8-9EE5-D6DF2CA457E5 v5
Section 4
Overview
10
are created in
11
can be
33