Resetting The Ied; Clearing And Acknowledging Via The Local Hmi - ABB Relion 650 Series Operation Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 500 128-UEN B
7.3
7.3.1
650 series 2.2 IEC
Operation manual
The time between selecting the object and giving a control
command is restricted by an adjustable timeout [(set by the
parameter tSelect for each object)]. When an object is selected, the
control command has to be given within this time.

Resetting the IED

Clearing and acknowledging via the local HMI

Use the Clear button to reset, acknowledge or clear all messages and indications,
including LEDs and latched outputs as well as registers and recordings. Pressing
the Clear button activates a view for selecting the reset function. Events and alarms
assigned to alarm LEDs can also be cleared with the Clear button.
1.
Press
to activate the Clear view.
All the items that can be cleared are shown.
GUID-0CFAED62-312B-449F-BB58-D49496EA1CC8 V2 EN-US
Figure 43:
Clear view
The content of the Clear menu depends on the configuration configured with
PCM600.
2.
Select the item to be cleared with
3.
Press
, select OK to confirm the selection or Cancel to cancel the
selection.
4.
To clear other items, repeat the steps.
Operating procedures
GUID-9880CE57-79DE-4949-B9FA-1E91ED2F5F4B v5
IEC13000236-1-en.vsd
or
.
Section 7
69