LED Operator Display
Cause
An external fault is being sent from
the master controller (PLC).
Problem with the PLC program
LED Operator Display
Cause
Non-compatible option connected to
the drive
LED Operator Display
Cause
Problem with the connectors between
the drive and CC-Link Option
LED Operator Display
Cause
CC-Link Option hardware fault
LED Operator Display
Cause
CC-Link Option hardware fault
YASKAWA ELECTRIC TOBP C730600 22B V1000 Option CC-Link Installation Manual
External Fault Input from CC-Link Option
EF0
The alarm function for an external device has been triggered.
⇒ Remove the cause of the external fault.
⇒ Reset the external fault input from the PLC device.
⇒ Check the program used by the PLC and make the appropriate
corrections.
CC-Link Option Fault (port A)
oFA00
CC-Link Option is not properly connected.
⇒ Connect an option that is compatible with the drive.
CC-Link Option Fault (port A)
oFA01
CC-Link Option is not properly connected.
⇒ Turn the power off and check the connectors between the drive and CC-
Link Option.
CC-Link Option Fault (port A)
oFA03
CC-Link Option self-diagnostics error
⇒ Replace the CC-Link Option. Contact Yaskawa for consultation.
CC-Link Option Fault (port A)
oFA04
CC-Link Option Flash write mode
⇒ Replace the CC-Link Option. Contact Yaskawa for assistance.
9 Troubleshooting
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
33