4 CC-Link Option Components
◆
CC-Link Option LED Display
Name
Color
L.RUN
Green
L.ERR
Red
SD
Red
RD
Red
◆
Setting Station Address
Set drive parameter F6-10 to a station address (Range 1 to 64) unique to the network. If set
to 0, the L.ERR light will turn on and a Station Address Error (AEr) will occur.
14
Table 4 CC-Link Operation LED Status
Indication
Operating Status
Status
ON
Normal operation
OFF
Timed out
ON
CRC error
During
OFF
communications
ON
Sending data
OFF
No data transfer
Detecting data
ON
received
OFF
Waiting for data
YASKAWA ELECTRIC TOBP C730600 22B V1000 Option CC-Link Installation Manual
Remarks
• Receiving data normally
• Timed out waiting to receive
• Logging onto the network
• During reset
• CRC error
• Station address setting error (F6-10 = 0)
• Normal communications
• During reset
• Sending data
Note: LED may appear to flash
with slower baud rates.
• No data being sent
• During reset
• Detecting data that was received
Note: LED may appear to flash
with slower baud rates.
• Data not yet received
• During reset