8 CC-Link Data Table
Device
Signal Name
RX3
Speed Agree
RX4
During Stall Prevention
RX5
During Undervoltage
RX6
Terminal P1 Function
RX7
Terminal P2 Function
RX8, 9 Reserved
RXA
CC-Link Option Fault
Monitoring Motor
RXB
Revolutions
RXC
Obtain Monitor Data
RXD
Frequency Setting Ready 1
RXE
Frequency Setting Ready 2
Command Code Execute
RXF
Complete
RX10
Reserved
to 19
RX1A Error
RX1B Remote Station Ready
RX1C
Reserved
to 1F
Note: If making frequent setting changes, use RYD (Frequency Reference 1 flag) for setting the
register. Using RYE (Frequency Reference 2 flag) too often can shorten the performance life of
the drive's internal memory.
30
Description
ON: Output frequency is between frequency reference
and the detection width set to L4-02.
Multi-function output: H2-02
Multi-function output: H2-03
Comm. error between drive and CC-Link device
ON: Currently monitoring motor revolutions.
ON: Monitor data has been updated.
ON: Displays the main frequency reference that has been
set.
ON: Displays the data set to d1-01 (Frequency Reference
1).
Note: Also sets the main frequency reference at the same
time.
ON: Displayed after the specified command code has
been executed.
RXF signal switches off when the RYF command is no
longer present.
ON: Fault occurred on the drive side.
ON: Drive is ready to operate.
YASKAWA ELECTRIC TOBP C730600 22B V1000 Option CC-Link Installation Manual
Default
(H2-02 = 0: During
Run)
(H2-03 = 2: Speed
Agree 1)
Data is stored in
remote register
RW
.
R1

Hide quick links: