Programming

POOGOAMMING
Each turbine flow meter is shipped with either a K-factor value or frequency data If frequency data is provided, the data must
be converted to a K-factor before programming the monitor K-factor information, when supplied, can usually be found on the
neck of the flow meter or stamped on the flow meter body The K-factor represents the number of pulses per unit of volume
The K-factor is needed to program the monitor readout

Programming Mode

Enter Program Mode
Press MENU to enter the programming mode The mode indicator changes from RUN to PROGRAM
Select Meter Size
At the METER prompt, press UP or OIGHT to scroll to the bore size of your meter Press ENTEO to save and advance to the
K-factor Units parameter
N
OTEE:
The meter connection size and the bore size are different For example, many of the one inch NPT turbines have bore
sizes that range from 3/8...1 in Be sure to use the correct bore size or the meter will report incorrect flows and totals
Enter The K-Factor Unit
Press UP or OIGHT to scroll to the K-factor unit of the meter Enter the unit that the meter was calibrated in
Example
If the meter was calibrated in US gallons, use PUL/GAL
Press ENTEO to save the K-factor unit and advance to the K FACTOR parameter
N
OTEE:
Unless otherwise specified, Blancett turbine flow meters are supplied with K-factors measured in pulses per gallon
(PUL/GAL) which will automatically convert to your desired units of measure
Enter The Meter's K-Factor
N
OTEE:
The K-factor supplied with the meter or calculated from calibration data is needed to set this parameter
To change the K-factor value, press OIGHT to select the digit that you wish to change Press UP to increment the digit until it
matches the meter's K-factor Repeat this process until all K-factor digits have been entered Press ENTEO to save the K-factor
and advance to RATE/TOTAL
Page 6
IO/SETUP
METER
K Factor Units
PUL/GAL
PUL/M3
K FACTOR
Units
GPM/GAL LPM/LIT
M3PH/M3
DSP
BOTH
TOTAL
Pulse Output
PULS ON
PULS OFF
PASSWORD
RST PSWD
DSY-PM-00278-EN-04
PUL/LTR
PUL/FT3
M3PD/M3 BPD/BBL
RATE
TEST
November 2017