Run Mode - Badger Meter B2800 User Manual

Flow monitor panel mount standard
Hide thumbs Also See for B2800:
Table of Contents

Advertisement

Select the Units of Measure
The monitor is programmed with five common rate/total unit options The monitor shows the rate/total unit that the display
is currently set for If the current selection is correct, press ENTEO once to advance to the DISPLAY FUNCTION parameter
To change the unit, press UP or OIGHT to scroll to the correct rate unit Press ENTEO to save and advance to the DISPLAY
FUNCTION parameter
Select the Display Function
The monitor displays RATE, TOTAL, alternates between BOTH rate and total or TEST If the current selection is correct, press
ENTEO to advance to the next parameter To change to an alternate display mode, press UP or OIGHT to scroll to the correct
display mode and press ENTEO to save and advance to the TOTALIZER PULSE OUTPUT parameter
The TEST function acts like a frequency counter and displays the raw input frequency being supplied to the frequency input
terminals This is very useful when troubleshooting flow problems
Totalizer Pulse Output
The pulse output parameter can be enabled or disabled When enabled this output generates 20 mS duration pulse for every
time the least significant digit of the totalizer increments The amplitude of the pulse is dependent on the voltage level of the
supply connected to the pulse output and is limited to a maximum 30V DC Press UP or OIGHT to scroll to ON or OFF Press
ENTEO to save and advance to the PASSWORD parameter
Password
The PASSWORD setting restricts access to PROGRAM mode Initially, the password is set to all zeros and any user can modify
the parameter settings in PROGRAM mode To change the password, enter any four digit code Press UP to increment the digit,
and OIGHT to advance to the next digit Press ENTEO to store the password and advance to RST PSWD The new password is
now required to enter PROGRAM mode With this password set, any user is able to reset the stored totals on the monitor
Oeset Password
The RST PSWD restricts resetting the totals on the monitor The PASSWORD must also be set to restrict the total reset Initially,
the password is set to all zeros and any user can reset the stored totals on the monitor To change the password, enter any four
digit code Press UP to increment the digit, and OIGHT to advance to the next digit After entering all digits, press ENTEO to
store the password and return to RUN mode The reset password is now required to reset the totals on the monitor
Oun Mode
Oeset Total
To reset the monitor total display, in RUN mode press MENU and ENTEO simultaneously If the RST PSWD has been set to
something other than the default, you must enter the new password before the monitor will reset The monitor flashes
TOTAL RST and returns to RUN mode at the conclusion of the reset procedure
Store Total
The current total can be manually stored in the monitor's flash memory Use this feature prior to replacing the battery Press
and hold ENTEO for 2 seconds The display responds with a flashing TOTALSVD and then returns to RUN mode
Automatic Store Total
The monitor is equipped with a store total feature that works automatically, saving the current total to flash memory The
frequency of saves depends on the power supply option chosen
Battery Powered: Once per hour and just before a low battery condition turns the unit off
Loop Powered: Once every ten minutes
November 2017
Selection
GPM/GAL
Gallons per minute
LPM/LIT
Liters per minute
M3PH/M3
Cubic meters per hour
M3PD/M3
Cubic meters per day
BPD/BBL
Oil barrels per day
DSY-PM-00278-EN-04
Oate
Total
Gallons
Liters
Cubic meters
Cubic meters
Oil barrels
Programming
Page 7