Power Derating - ABB TRIO-5.8-TL-OUTD-S Product Manual

Table of Contents

Advertisement

TRIO-8.5-TL-OUTD
TRIO-8.5-TL-OUTD-S
Pout% (320Vdc) Eff. (320Vdc)
20
95.1
30
95.9
50
96.6
75
96.7
100
96.5
Pout% (620Vdc) Eff. (620Vdc)
20
97.1
30
97.7
50
98.0
75
98.0
100
97.7
Pout% (800Vdc) Eff. (800Vdc)
20
95.7
30
96.7
50
97.3
75
97.5
100
97.5
P
ower derating
100
99
98
97
96
95
94
93
92
91
90
0%
10%
20%
30%
In order to allow inverter operation in safe thermal and electrical condi-
tions, the unit automatically reduces the value of the power fed into the
grid.
Power limiting may occur due to:
• Adverse environmental conditions (thermal derating)
• Percentage of output power (value set by the user)
• Grid voltage over frequency (mode set by user)
• Grid over voltage U>10min Der. (enabling carried out by user)
• Anti-islanding
• Grid under voltage
• Input voltage values too high.
• Input current values too high.
- 25 -
Efficiency curves
40%
50%
60%
70%
% of Rated Output Power
2 - Characteristics
320 Vdc
620 Vdc
800 Vdc
80%
90%
100%