The ET 200pro EtherNet/IP module

3.3 Parameters for the ET 200pro EtherNet/IP module

3.3
Parameters for the ET 200pro EtherNet/IP module
Parameter assignment
Parameters for the ET 200pro EtherNet/IP module are set by using the EIP ET200
Configuration Tool software. After loading new parameters into the interface module, the
parameters take effect immediately.
The following table describes the parameters of the ET 200pro EtherNet/IP interface module
as they appear in the Configuration Tool:
Parameter
Operation for ref. <> actual conf.
Identifier-related diagnostics
Submodule status
Channel-related diagnostics
Option handling
Parameter description
Operation for ref. <> actual conf.
If this parameter is enabled and:
● you hot-swap an electronic module, this will not cause a failure of the ET 200pro station.
● the preset and actual configurations do not match, ET 200pro can still exchange data with
the PLC.
If this parameter is disabled and:
● you hot-swap an electronic module, this will cause a failure of the ET 200pro station.
● the preset and actual configurations do not match, ET 200pro cannot exchange data with
the PLC.
Identifier-related diagnostics
This parameter has no effect for the ET 200pro EtherNet/IP module. All of the diagnostic
data is always available through the Adapter Object.
Submodule status
This parameter has no effect for the ET 200pro EtherNet/IP module. All of the diagnostic
data is always available through the Adapter Object.
Channel-related diagnostics
This parameter has no effect for the ET 200pro EtherNet/IP module. All of the diagnostic
data is always available through the Adapter Object.
22
Value range
enable disable
enable disable
enable disable
enable disable
not currently supported
ET 200pro distributed I/O EtherNet/IP interface module
Manual, 03/2016, A5E32861915-AB
Default
disable
enable
enable
enable