The ET 200pro EtherNet/IP module

3.6 Replacing a faulty ET 200pro EtherNet/IP module

3.6
Replacing a faulty ET 200pro EtherNet/IP module
When you download a new configurations or new network parameters to the ET 200pro
EtherNet/IP module, the data is stored in internal flash memory.
Replacement procedure
Follow this procedure to replace the ET 200pro EtherNet/IP module:
1. Using the EIP ET200 Configuration Tool, upload the current configuration.
2. Replace the ET 200pro EtherNet/IP module.
3. Power up the replacement module.
4. Restore the connections.
5. Download the configuration to the module.
You can now use the replacement module.
Note
If you are not also replacing the connection module, you can skip steps 1 and 5 above
because your data is stored in the connection module flash memory.
28
ET 200pro distributed I/O EtherNet/IP interface module
Manual, 03/2016, A5E32861915-AB