Option handling
This parameter is not currently supported.
3.4

Faults

Configuration faults
Faults in the electronic module configuration and parameterization data are handled slightly
differently depending on when they are detected.
Regardless of the detection time, the following occur:
● The Adapter Object AdapterStatus attribute indicates the appropriate code.
● The Identity Object Status attribute indicates a minor recoverable fault.
When the fault is detected at power-up or as a result of a hot swap when no I/O connections
are open:
● An attempt to open I/O connections results in a Device State Conflict error.
A fault detected as a result of a hot-swap when one or more I/O connections are open result
in the following behavior:
● If the IO_StatusEnable attribute is TRUE, a fault is indicated in the I/O Status byte at the
beginning of the input data packet.
● Output data from the scanner is ignored.
● Any attempt to allocate I/O connections is rejected by the device.
You can recover from the configuration fault by:
● installing or removing I/O modules to make the actual configuration match the
user-defined configuration; and/or
● changing the configuration data to match the actual configuration.
The I/O configuration is reapplied immediately after a configuration download from the
EIP ET200 Configuration Tool, and at module startup.
Electronic module faults
When an I/O connection is active, faults in electronic modules are reported as follows:
● If the IO_StatusEnable attribute is TRUE, a fault is indicated in the I/O Status byte at the
beginning of the input data packet.
● The appropriate Slot Object instance SlotStatus attribute and Channel<n>Status
attribute(s) indicate the nature of the fault.
● The I/O status LED state is flashing red when I/O is active.
ET 200pro distributed I/O EtherNet/IP interface module
Manual, 03/2016, A5E32861915-AB
The ET 200pro EtherNet/IP module
3.4 Faults
23