CHAPTER 7: COMMANDS AND TARGETS
being the highest priority. For example, if all three SFP modules fail, then the third SFP target is activated. If the third
SFP module failure resolves, then the second SFP target is activated.
AUTHENTICATION FAIL
Latched target message: No.
Description of problem: The number of failures threshold was exceeded.
What to do: Wait for the lockout interval and try to authenticate again.
FIRMWARE LOCK
Message: "Unauthorized firmware attempt"
Latched target message: No.
Description of problem: A firmware upgrade operation was attempted while the lock relay setting was enabled.
What to do: Ask the Supervisor to unlock the relay and try again.
SETTING LOCK
Message: "Unauthorized setting write"
Latched target message: No.
Description of problem: A setting write was attempted while the lock relay setting was enabled.
What to do: Ask the Supervisor to unlock the settings and try again.
SERVER UNAVAILABLE
Message: "An attempt to contact the Radius server has failed"
Latched target message: No.
Description of problem: The RADIUS authentication server is unavailable.
What to do: Verify network connectivity and try again.
DOS PARTITION ALARM:
SELF-TEST ERROR
Description of problem: There is a problem with the Compact Flash memory in the CPU module.
How often the test is performed: On relay power-up and afterwards once every 24 hours.
What to do: Contact the factory.
PROTOTYPE FIRMWARE:
Self Test Error
Description of problem: Seen until the builds is tagged as being 'release candidate' or 'gold' builds.
What to do: Update firmware to either of these builds.
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL