GE L60 Instructions Manual page 401

Line phase comparison system
Hide thumbs Also See for L60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
87PC SIGNAL:
Mixed I_2-K*I_1
87PC MIXED SIGNAL K:
0.20
87PC MIXED SIGNAL
REF ANGLE: 0°
87PC FDL PICKUP:
0.50 pu
87PC FDL AUX:
Off
87PC FDH PICKUP:
0.75 pu
87PC FDH AUX:
Off
87PC FDH SUPV:
Off
87PC CH1 ASYMMETRY:
0.0 ms
87PC CH2 ASYMMETRY:
0.0 ms
87PC CH1 DELAY:
0.0 ms
87PC CH2 DELAY:
0.0 ms
87PC CH1 RX VOLT:
12.0 V
87PC CH2 RX VOLT:
12.0 V
87PC TRIP SECURITY:
First Coincidence
87PC SECOND COINCID
TIMER: 40 ms
87PC STABILITY
ANGLE: 75°
87PC ENHANCED STAB
ANGLE: 110°
87PC PICKUP DELAY:
0 ms
87PC STOP TX:
Off
87PC TX RESET DELAY:
0 ms
87PC RESET DELAY:
30 ms
87PC TRANS BLOCK
PICKUP: 0.030 s
87PC TRANS BLOCK
RESET: 0.030 s
GROUPED ELEMENTS
Range: Mixed I_2–K*I_1, Mixed I_1+I_2/K, 3I_0
Range: 0.00 to 0.25 in steps of 0.01
Range: 0 to 359° in steps of 1
Range: 0.02 to 15.00 pu in steps of 0.01
Range: FlexLogic operand
Range: 0.05 to 15.00 pu in steps of 0.01
Range: FlexLogic operand
Range: FlexLogic operand
Range: –5.0 to 5.0 ms in steps of 0.1
Range: –5.0 to 5.0 ms in steps of 0.1
Range: 0.0 to 30.0 ms in steps of 0.1
Range: 0.0 to 30.0 ms in steps of 0.1
Range: 0.0 to 125.0 V in steps of 0.1
Range: 0.0 to 125.0 V in steps of 0.1
Range: First Coincidence, Enhanced
Range: 10 to 200 ms in steps of 1
Range: 40 to 140° in steps of 5
Range: 40 to 180° in steps of 5
Range: 0 to 50 ms in steps of 1
Range: FlexLogic operand
Range: 0 to 1000 ms in steps of 1
Range: 0 to 200 ms in steps of 1
Range: 0 to 65.535 s in steps of 0.001
Range: 0 to 65.535 s in steps of 0.001
5
5-193

Advertisement

Table of Contents
loading