GE L60 Instructions Manual page 415

Line phase comparison system
Hide thumbs Also See for L60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
This setting is forced to "Disabled" if a phase VT bank is not assigned at either source 3 or source 4.
The figure shows possible configurations.
— This setting selects an input to block charging current compensation. This input is typically the
CHARGE COMPENST BLOCK
VT fuse fail element of the source, where the three-phase VT is configured with this setting to block compensation.
Blocking charging current compensation at one end of the line does not block charging current compensation on the other
end. However, even with compensation operating at one end, half (or one-third) of the charging current is still removed
from the net phase comparison current. Alternatively, switch to another setting group with more conservative phase
comparison settings during a VT fuse fail condition.
and
POSITIVE
ZERO SEQUENCE CAPACITIVE REACTANCE
the protected line are required for charging current compensation calculations. The line capacitive reactance values are
entered in primary kilo-ohms for the total line length.
If shunt reactors are also installed on the line, the resulting value entered in the
settings are calculated as follows:
SEQ CAPACITIVE REACTANCE
1.
No shunt reactors on the line or reactor current is subtracted from the line current, forcing the L60 to measure the
uncompensated by shunt reactors load/fault current plus the full charging current.
2.
Three-reactor arrangement — Three identical line reactors (X
3.
Four-reactor arrangement — Three identical line reactors (X
connected between reactor-bank neutral and the ground.
X
= the total line positive-sequence capacitive reactance
1line_capac
X
= the total line zero-sequence capacitive reactance
0line_capac
X
=the total reactor inductive reactance per phase. If identical reactors are installed at both ends of the line, the
react
inductive reactance is divided by 2 (or 3 for a three-terminal line) before inserting in the above equations. If the
reactors installed at both ends of the line are different, the following equations apply:
3.1.
For a two-terminal line
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
Figure 5-105: Charging current compensation configurations
— The values of positive and zero sequence capacitive reactance of
POS SEQ CAPACITIVE REACTANCE
) solidly connected phase to ground.
react
) wye-connected with the fourth reactor (X
react
GROUPED ELEMENTS
5
and
ZERO
Eq. 5-8
Eq. 5-9
)
react_n
Eq. 5-10
5-207