RECORDS

Loop impedance is defined as Z##=|Z##| Angle=R##+jX##, in secondary ohms and ## is the loop indication (AB, BC, CA,
AG, BG, and CG respectively).
They are calculated as
per the following equations.
where
VA, VB, VC are phase voltage phasors in secondary volts
IA, IB, IC are current phasors in secondary amps
I0 is the zero sequence current phasors in secondary amps
IG is the ground current from the parallel line scaled to the source phase CT in secondary amps
Z0/Z1 is the zero sequence impedance to positive sequence impedance ratio
Z0M/Z1 is mutual zero sequence impedance to positive sequence impedance ratio, both are settings taken from the first
enabled ground distance zone (count from zone 1 to zone 5)
ZAG, ZBG, ZCG are calculated only if at least one ground distance zone is enabled; otherwise all the metering quantities for
ground distance impedance (ZAG, ZBG, and ZCG) are reset to zero, including magnitude and angle. Note that VTs of the
distance source must be connected in Wye if the ground distance element is enabled.
6.5 Records
6

6.5.1 Fault reports

ACTUAL VALUES  RECORDS  FAULT REPORTS  FAULT REPORT 1(15)
NO FAULTS TO REPORT
or
 FAULT REPORT 1
6-24
CG LOOP IMPEDANCE
ANGLE: 0.00 DEG
FAULT 1
LINE ID: SRC 1
FAULT 1
DATE:
2000/08/11
FAULT 1
TIME:
00:00:00.000000
FAULT 1
TYPE:
ABG
FAULT 1
LOCATION
00.0 km
FAULT 1
RECLOSE
SHOT: 0
FAULT 1
LOOP
RESIST: 0.00 Ohms
CHAPTER 6: ACTUAL VALUES
Range: SRC 1, SRC 2
Range: YYYY/MM/DD
Range: HH:MM:SS.ssssss
Range: not available if the source VTs are in the
"Delta" configuration
Range: not available if the source VTs are in the
"Delta" configuration
Range: where applicable
Range: 0 to 327.67 Ohms
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
Eq. 6-3
Eq. 6-4