GE L60 Instructions Manual page 556

Line phase comparison system
Hide thumbs Also See for L60:
Table of Contents

Advertisement

CONTROL ELEMENTS
The autoreclose scheme is intended for use on transmission lines with circuit breakers operated in both the single pole and
three pole modes, in one or two breaker arrangements. The autoreclose scheme provides four programs with different
operating cycles, depending on the fault type. Each of the four programs can be set to trigger up to four reclosing
attempts. The second, third, and fourth attempts always perform three-pole reclosing and have independent dead time
5
delays.
When used in two breaker applications, the reclosing sequence is selectable. The reclose signal can be sent to one
selected breaker only, to both breakers simultaneously or to both breakers in sequence (one breaker first and then, after a
delay to check that the reclose was successful, to the second breaker). When reclosing in sequence, the first breaker
should reclose with either the single-pole or three-pole dead time according to the fault type and reclose mode; the second
breaker should follow the successful reclosure of the first breaker. When reclosing simultaneously, for the first shot both
breakers should reclose with either the single-pole or three-pole dead time, according to the fault type and the reclose
mode.
The signal used to initiate the autoreclose scheme is the trip output from protection. This signal can be single pole tripping
for single phase faults and three phase tripping for multi-phase faults. The autoreclose scheme has five operating states.
Table 5-41: Autoreclose states
State
Enabled
Disabled
Reset
Reclose in progress
Lockout
Autoreclose programs
The autorecloser provides four programs that can cause from one to four reclose attempts (shots). After the first shot, all
subsequent recloses are always three-pole. If the maximum number of shots selected is "1" (only one reclose attempt) and
the fault is persistent, after the first reclose the scheme goes to lockout upon another Initiate signal.
For the three-pole reclose programs (modes 3 and 4), an
connection with the tripping logic to cause a three-pole trip for single-phase faults.
5-348
AR TRANSFER 1 TO 2:
No
AR TRANSFER 2 TO 1:
No
AR BKR1 FAIL OPTION:
Continue
AR BKR2 FAIL OPTION:
Continue
AR 1-P DEAD TIME:
1.00 s
AR BKR SEQUENCE:
1-2
AR TRANSFER TIME:
4.00 s
AR BUS FLT INIT:
Off
AR EVENT:
Disabled
Characteristic
Scheme is permitted to operate
Scheme is not permitted to operate
Scheme is permitted to operate and shot count is reset to 0
Scheme has been initiated but the reclose cycle is not finished (successful or not)
Scheme is not permitted to operate until reset received
Range: Yes, No
Range: Yes, No
Range: Continue, Lockout
Range: Continue, Lockout
Range: 0 to 655.35 s in steps of 0.01
Range: 1, 2, 1&2, 1–2, 2–1
Range: 0 to 655.35 s in steps of 0.01
Range: FlexLogic operand
Range: Enabled, Disabled
FlexLogic operand is set. This operand can be used in
AR FORCE 3-P
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS

Advertisement

Table of Contents
loading

Table of Contents