GE L60 Instructions Manual page 685

Line phase comparison system
Hide thumbs Also See for L60:
Table of Contents

Advertisement

CHAPTER 9: THEORY OF OPERATION
Single pole operations are based on use of the phase selector to identify the type of the fault, to eliminate incorrect fault
identification that can be made by distance elements in some circumstances and to provide trip initiation from elements
that are not capable of any fault type identification, such as high-set negative-sequence directional overcurrent element.
The scheme is also designed to make use of the advantages provided by communications channels with multiple-bit
capacities for fault identification.
The trip output element receives requests for single and three-pole trips and three-pole reclose initiation, which it then
processes to generate outputs that are used to
Determine whether a single or three-pole operation is to be performed
Initiate tripping of breaker poles A, B, and C, either individually or as a group
Initiate breaker failure protection for phases A, B, and C, either individually or as a group
Notify the open pole detector when a single pole operation is imminent
Initiate either single or three-pole reclosing
Notify the phase selector when a trip operation is imminent
When notified that a single pole operation has been initiated, the open-pole detector
Initiates blocking of protection elements that can potentially maloperate when a breaker pole is open
Instructs the phase selector to de-assert all outputs, as an open pole invalidates calculations
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
Figure 9-28: Single-pole operation
SINGLE-POLE TRIPPING
9-37
9

Advertisement

Table of Contents
loading

Table of Contents