GE L60 Instructions Manual page 440

Line phase comparison system
Hide thumbs Also See for L60:
Table of Contents

Advertisement

GROUPED ELEMENTS
CHAPTER 5: SETTINGS
Figure 5-126: Ground distance zones 2 and higher pickup logic
5
Ground directional supervision
A dual (zero-sequence and negative-sequence) memory-polarized directional supervision applied to the ground distance
protection elements has been shown to give good directional integrity. However, a reverse double-line-to-ground fault can
lead to bad operation of the ground element in a sound phase if the zone reach setting is increased to cover high
resistance faults.
Ground distance zones 2 and higher use an additional ground directional supervision to enhance directional integrity. The
element's directional characteristic angle is used as a maximum torque angle together with a 90° limit angle.
The supervision is biased toward operation in order to avoid compromising the sensitivity of ground distance elements at
low signal levels. Otherwise, the reverse fault condition that generates concern has high polarizing levels so that a correct
reverse fault decision can be reliably made.
The supervision for zones 2 and 3 is removed during open pole conditions.
5-232
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL