GE L60 Instructions Manual page 555

Line phase comparison system
Hide thumbs Also See for L60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
AR BLOCK BKR1:
Off
AR CLOSE TIME BKR 1:
0.10 s
AR BKR MAN CLOSE:
Off
AR BLK TIME UPON MAN
CLS: 10.00 s
AR 1P INIT:
Off
AR 3P INIT:
Off
AR 3P TD INIT:
Off
AR MULTI-P FAULT:
Off
BKR ONE POLE OPEN:
Off
BKR 3 POLE OPEN:
Off
AR 3-P DEAD TIME 1:
0.50 s
AR 3-P DEAD TIME 2:
1.20 s
AR 3-P DEAD TIME 3:
2.00 s
AR 3-P DEAD TIME 4:
4.00 s
AR EXTEND DEAD T 1:
Off
AR DEAD TIME 1
EXTENSION: 0.50 s
AR RESET:
Off
AR RESET TIME:
60.00 s
AR BKR CLOSED:
Off
AR BLOCK:
Off
AR PAUSE:
Off
AR INCOMPLETE SEQ
TIME: 5.00 s
AR BLOCK BKR2:
Off
AR CLOSE TIME BKR2:
0.10 s
Range: FlexLogic operand
Range: 0.1 to 655.35 s in steps of 0.01
Range: FlexLogic operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic operand
Range: 0 to 655.35 s in steps of 0.01
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0 to 655.35 s in steps of 0.01
Range: FlexLogic operand
Range: 0.1 to 655.35 s in steps of 0.01
CONTROL ELEMENTS
5
5-347