GE L60 Instructions Manual page 522

Line phase comparison system
Hide thumbs Also See for L60:
Table of Contents

Advertisement

CONTROL ELEMENTS
Number
1
2
3
4
5
The voltages V1 and V2 are matched automatically so that the corresponding voltages from the two sources are used
to measure conditions. A phase to phase voltage is used if available in both sources; if one or both of the Sources have
only an auxiliary voltage, this voltage is used. For example, if an auxiliary voltage is programmed to VAG, the
synchrocheck element automatically selects VAG from the other source. If the comparison is required on a specific
voltage, the user can externally connect that specific voltage to auxiliary voltage terminals and then use this "Auxiliary
Voltage" to check the synchronism conditions.
If using a single CT/VT module with both phase voltages and an auxiliary voltage, ensure that only the auxiliary
voltage is programmed in one of the sources to be used for synchrocheck. An exception is that synchronism cannot
be checked between Delta connected phase VTs and a Wye connected auxiliary voltage.
2.
The relay measures frequency and Volts/Hz from an input on a given source with priorities as established by the
5
configuration of input channels to the source. The relay uses the phase channel of a three-phase set of voltages if
programmed as part of that source. The relay uses the auxiliary voltage channel only if that channel is programmed
as part of the Source and a three-phase set is not.
5-314
V1 or V2 (source Y)
V2 or V1 (source Z)
Phase VTs and
Phase VTs and
Auxiliary VT
Auxiliary VT
Phase VTs and
Phase VT
Auxiliary VT
Phase VT
Phase VT
Phase VT and Auxiliary
Auxiliary VT
VT
Auxiliary VT
Auxiliary VT
Auto-selected combination
Source Y
Source Z
Phase
Phase
Phase
Phase
Phase
Phase
Phase
Auxiliary
Auxiliary
Auxiliary
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Auto-selected
voltage
VAB
VAB
VAB
V auxiliary
(as set for source Z)
V auxiliary
(as set for selected
sources)