GE L60 Instructions Manual page 406

Line phase comparison system
Hide thumbs Also See for L60:
Table of Contents

Advertisement

GROUPED ELEMENTS
CHAPTER 5: SETTINGS
In single phase comparison schemes, coincidence of the local and remote squares is detected during half the power cycle
only, positive or negative. As a result, some delay in operation can be expected under unfavorable fault inception. This
weakness of the single phase comparison schemes is eliminated in dual phase comparison schemes but cost of the
communication link is higher.
Some advantages of dual phase comparison and two frequency FSK PLC are incorporated in the unblocking scheme. Since
there is no third or guard frequency available, the PLC low frequency signal serves as the guard frequency for some logic
implemented in this scheme. Tripping is permitted if the FDL relay sees the change in received signal form low to high
(indicated that communication link is healthy and remote relay detected the fault) within 20 ms after fault is detected. If
the PLC low frequency has not being received prior the fault detection, the trip output is blocked as well. Another
enhancement of this scheme is the trip window defined by the
setting. This logic allows the
87PC CHNL LOSS TRIP WINDOW
relay to make a trip decision within this time if the PLC signal was lost in the course of the fault.
The phase comparison function can be used for three-terminal line protection and breaker-and-a-half configuration. The
feature combines the advantages of the modern digital relay with the traditional analog principle approach. Pulses
received from a PLC are digitally sampled at 64 samples per cycle, providing excellent resolution. This also eliminates
carrier building-up and tailing-off problems, since the voltage threshold for received pulses is user-programmable. If a
pulse received from PLC is consciously distorted and is not equal to half of the sinewave, it can be adjusted with the
87PC
and
settings. All phase comparison signals are captured and available in
CH1 ASYMMETRY
87PC CH2 ASYMMETRY
oscillography for commissioning, troubleshooting, and analysis purposes. The L60 features excellent stability during
channel noise due to the high sampling rate of the received signal, and the unique integrator makes the digital phase-
comparison relay fully equivalent to analogue phase-comparison relays.
The following figure illustrates the phase comparison logic. The choice of the scheme must made by protection and control
engineer according to the communication equipment employed, requirements of trip speed, and reliability.
5
5-198
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL

Advertisement

Table of Contents
loading

Table of Contents