GE L60 Instructions Manual page 402

Line phase comparison system
Hide thumbs Also See for L60:
Table of Contents

Advertisement

GROUPED ELEMENTS
The phase comparison tripping scheme menu provides the main setup for the phase comparison relay.
See the Application of Settings chapter for more information on individual settings.
87PC SCHEME SELECT
2TL-TR-SPC-2FC — Two-terminal line, permissive tripping, single phase comparison, two frequency channel.
2TL-BL-SPC-2FC — Two-terminal line, blocking scheme, single phase comparison, two frequency channel.
2TL-UB-DPC-2FC — Two-terminal line, unblocking, dual phase comparison, two frequency channel (FSK PLC only);
scheme cannot be used for breaker-and-a-half applications.
2TL-TR-DPC-3FC — Two-terminal line, permissive tripping, dual phase comparison, three frequency channel.
2TL-BL-DPC-3FC — Three-terminal line, blocking scheme, dual phase comparison, three frequency channel.
3TL-TR-SPC-2FC — Three-terminal line, permissive tripping scheme, single phase comparison, two frequency channel
carrier to two other terminals.
5
3TL-BL-SPC-2FC — Three-terminal line, blocking scheme, single phase comparison, two frequency channel carrier to
two other terminals.
3TL-TR-DPC-3FC — Three-terminal line, permissive tripping scheme, dual phase comparison, three frequency channel
carrier to two other terminals.
3TL-BL-SPC-3FC — Three-terminal line, blocking scheme, dual phase comparison, three frequency channel carrier to
two other terminals.
A two-frequency channel (2FC) can be either amplitude modulated (AM) on-off carrier or a high-low frequency shift
keying (FSK) system.
In blocking schemes, the open breaker echo element must be disabled.
— Selects a Flexlogic operand that blocks operation of the phase comparison scheme (for example, an
87PC BLOCK
operand that indicates operation of a communications channel failure detector).
87PC SIGNAL SOURCE
dual-breakers with CTs summed externally) or from two separate sources (breaker-and-a-half or ring configurations),
where currents from both CTs are fed into the L60 individually.
— A mixed I_2 – K × I_1 signal, mixed I_1+I_2 / K signal, or single 3I_0 signal can be chosen as the operating
87PC SIGNAL
signal for the FDH and FDL detectors and positive/negative square pulses generation. The constant K in the mixed
excitation signal is adjustable.
87PC MIXED SIGNAL K
the mixed I_1+I_2 / K mode, the setting range is limited from 0.08 to 0.25.
87PC MIXED SIGNAL REF ANGLE
("Mixed I_2-K*I_1") and specifies a leading angular shift for the originally developed operating signal. The operating signal
is always developed taking phase A as reference for calculating symmetrical components. This setting can be used to
control the angular position of the operating current with respect to the voltage of any phase that can be used by the line
carrier in a particular application. This allows minimizing the impact of positive corona on dependability of single-
comparison blocking schemes. Effectively this setting shifts the transmitted pulses in time with the intent to minimize—for
5-194
87PC CHNL LOSS TRIP
WINDOW: 0 msec
87PC HIGH-SPEED TRIP
CONTACT 1: Off
87PC HIGH-SPEED TRIP
CONTACT 2: Off
87PC TARGET:
Self-Reset
87PC EVENTS:
Disabled
— Selects the phase comparison element scheme logic as follows:
— Selects whether current is supplied from one current source (either single-breaker CT application or
— Selects the K factor used in the mixed excitation operating signals I_2 – K × I_1 and I_1+I_2 / K. For
— This setting applies exclusively to the negative-sequence mixed mode operating current
Range: 0 to 500 ms in steps of 1
Range: Off, available contact outputs
Range: Off, available contact outputs
Range: Self-Reset, Latched, Disabled
Range: Disabled, Enabled
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS