Siemens Building Technologies
HVAC Products
8
Function block "Plant type"
This function block only contains the selection of the plant type.
8.1
Operating line
Line
Function, parameter
51
Plant type
8.2
General
When commissioning the plant, the respective plant type must be entered first. This
ensures that the functions required for the specific type of plant, the parameters and
operating lines for the settings and displays will be activated.
All plant-specific variables and operating lines existing for the other plant types will then
be hidden. They will not be displayed.
Example for an entry (selection of plant type 1–2)
Basic Documentation RVL471
8 Function block "Plant type"
Unit
Factory
setting
1−1
1
= heating circuit type 1
2
= d.h.w. circuit type 2
Range
1−0 ... 6−5
35/118
CE1P2524E
23.10.2002