Utility Package (Gx Configurator-Ct); Utility Package Functions - Mitsubishi QD60P8-G User Manual

Melsec-q series, channel isolated pulse input module
Table of Contents

Advertisement

6 UTILITY PACKAGE (GX Configurator-CT)

CHAPTER 6 UTILITY PACKAGE (GX Configurator-CT)

6.1 Utility Package Functions

Function
Make initial setting for operating the QD60P8-G for each channel.
Set the values of the items which require initial setting.
[Setting items]
• CH
Comparison output selection
• CH
Comparison output setting value
• CH
Movement averaging processing selection
Initial setting
• CH
Number of movement averaging processing
• CH
Pre-scale function selection
• CH
Pre-scale setting value
(The initially set data are registered to the programmable controller CPU parameters, and when the
6
programmable controller CPU is set to the RUN status, they are written to the QD60P8-G automatically.)
Set the buffer memory batch to be automatically refreshed for each channel of the QD60P8-G.
[Auto refresh target buffer memory values]
• Sampling pulse number
• Comparison output selection
• Comparison output setting value
• Movement averaging processing selection
• Number of movement averaging processing
Auto refresh
• Pre-scale function selection
setting
• Pre-scale setting value
• Accumulating count value
• Input pulse value
• Overflow detection flag
• Counter reset request
(The values stored in the automatically refreshed QD60P8-G buffer memory are read automatically when
the END instruction of the programmable controller CPU is executed.)
Monitors and tests the buffer memory and I/O signals for the QD60P8-G.
Monitor/Test
• X/Y Monitor/Test
• CH
Monitor/Test
6 - 1
The counter module utility package (GX Configurator-CT) is software designed to
make initial setting, auto refresh setting, monitor/test of the QD60P8-G using dedicated
screens, without being conscious of the I/O signals and buffer memory.
Use the utility package with GX Developer (SW4D5C-GPPW-E or later).
The following table gives the lists the functions of the utility package.
Utility package (GX Configurator-CT) function list
Details
• CH
Alarm output selection
• CH
Alarm output setting value upper/upper limit
• CH
Alarm output setting value upper/lower limit
• CH
Alarm output setting value lower/upper limit
• CH
Alarm output setting value lower/lower limit
• CH
Count cycle change function selection
• CH
Count cycle setting value
• Carry over detection flag
• Carry over reset request
• Error code
• Alarm output selection
• Alarm output flag
• Alarm output setting value upper/upper limit
• Alarm output setting value upper/lower limit
• Alarm output setting value lower/upper limit
• Alarm output setting value lower/lower limit
• Count cycle change function selection
• Count cycle setting value
MELSEC-Q
Reference
Section 6.4
Section 6.5
Section 6.6
6 - 1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sw0d5c-qctu-e

Table of Contents