4 SETUP AND PROCEDURE BEFORE OPERATION

4.5 Switch Setting for Intelligent Function Module

Switch No.
Switch 1
Input voltage selection
Pulse edge selection
Switch 2
Linear counter or Ring
counter selection
4 - 8
Settings for QD60P8-G input voltage selection, pulse edge selection, linear counter or
ring counter selection, and input filter setting can be made by the GX Developer
intelligent function module switch setting.
Make the intelligent function module switch setting in the "I/O assignment setting" PLC
parameter of the QCPU using GX Developer.
• The intelligent function module switch has switches 1 to 5, and is set at 16 bits data.
• If the intelligent function module switch setting is not operated, the default setting for
switches 1 to 5 is 0.
The settings made with the intelligent function module switches are made valid after
power-on or programmable controller CPU reset. You cannot change the settings
during operation.
Setting items
b15
Setting details/bit assignment
b15
b12
b8
b4
b0
Setting items
Not used
CH1 Input voltage
CH2 Input voltage
CH3 Input voltage
CH4 Input voltage
CH5 Input voltage
CH6 Input voltage
CH7 Input voltage
CH8 Input voltage
b12
b8
b4
b0
Setting items
CH1 Pulse edge
CH2 Pulse edge
CH3 Pulse edge
CH4 Pulse edge
CH5 Pulse edge
CH6 Pulse edge
CH7 Pulse edge
CH8 Pulse edge
CH1 Linear/Ring counter
CH2 Linear/Ring counter
CH3 Linear/Ring counter
CH4 Linear/Ring counter
CH5 Linear/Ring counter
CH6 Linear/Ring counter
CH7 Linear/Ring counter
CH8 Linear/Ring counter
Meaning
0:12 to 24VDC
1:5VDC
Meaning
0:Rise
edge
1:Fall
edge
Setting items
Meaning
0:Linear
counter
1:Ring
counter
MELSEC-Q
Default value
0000
H
0000
H
4 - 8