3 SPECIFICATIONS
Device
Signal name
No.
X10
CH1
X11
CH2
X12
CH3
X13
CH4
Accumulating
counter
comparison
flag
X14
CH5
X15
CH6
X16
CH7
X17
CH8
3 - 6
OFF: Accumulating
count value
Comparison
output setting
value
ON : Accumulating
count value
Comparison
output setting
value
*1: Initial value set at power-on or when the programmable controller CPU is reset.
• This signal turns ON if the "accumulating count value"
reaches or exceeds the "comparison output setting value".
The "accumulating count value" is stored into the buffer
memory for each channel. Set the "comparison output
setting value" to the buffer memory for each channel.
(Refer to Section 3.4.2 for details.)
• This signal remains ON until the comparison signal reset
request (Y10 to Y17) turns ON.
• Once turned OFF, this signal does not turn ON until the
accumulating count value reaches the comparison output
setting value again after it has been reset.
Executed by QD60P8-G
Executed by sequence program
Accumulating count value
Comparison output
setting value
Accumulating counter
OFF
comparison flag
(X10 to X17)
Comparison signal
OFF
reset request
(Y10 to Y17)
MELSEC-Q
Details
Count cycle
setting value
ON
ON
Initial
value
*1
OFF
3 - 6