5 DETAILS AND SETTING OF FUNCTIONS

5.1.4 Count cycle changing

Item
Count cycle change
function selection
Count cycle setting
value
5 - 4
This section describes how to change the count cycles of the sampling pulse number
and accumulating count value.
To change the count cycle, set "1: Count cycle change function selection valid" in the
"count cycle change function selection" of the buffer memory. (Whether the function is
valid or invalid can be selected on each channel.)
Further, set the count cycle in the "count cycle setting value" of the buffer memory.
Setting value
0: Count cycle change function
selection invalid *
1: Count cycle change function
selection valid
0: 1s
1: 100ms
2: 200ms
3: 500ms
*: When "count cycle change function selection invalid" is set, the count cycle is 1s
(fixed).
POINT
• If the setting value is other than the above values, a count cycle setting range
outside error (error code: 600) occurs. To clear the error, turn ON the error reset
request (Y8 to YF) of the corresponding channel. After this, set a correct value
and then turn ON the operating condition setting request flag (Y1).
• The settings are reflected on the module by turning ON the operating condition
setting request flag (Y1) after setting the values to the buffer memory.
Buffer memory address
CH1
CH2
CH3
CH4
23
55
87
119
24
56
88
120
MELSEC-Q
CH5
CH6
CH7
CH8
151
183
215
247
152
184
216
248