5 DETAILS AND SETTING OF FUNCTIONS
Item
Accumulating count value
Overflow detection flag
Counter reset request
5 - 6
• Overflow error
An overflow error (error code: 100) occurs if the "accumulating count value" of
the buffer memory exceeds 99999999 when the count type is the linear counter.
If the overflow error occurs, count operation is stopped, and the "accumulating
count value" of the buffer memory does not change from 99999999 if pulses are
input. Also, the "sampling pulse number" of the buffer memory is reset.
The overflow error is cleared by setting "1" in the "counter reset request" of the
buffer memory. Count operation is resumed after the error is cleared. The error is
also cleared by turning ON the error reset request (Y8 to YF). To resume count
operation, however, turn ON the operating condition setting request flag (Y1) or
set "1" in the "counter reset request" of the buffer memory.
When checking for the module error at occurrence of an overflow error, click the
[Diagnosis] - [System monitor] menu on GX Developer and monitor the system.
Read value/Setting value
0 to 99999999
0: No overflow detection (OFF)
1: Overflow detection (ON)
1: Reset request
(The value automatically
turns to "0" after completion
of a counter reset.)
Buffer memory address
CH1
CH2
CH3
CH4
8
40
72
104
9
41
73
105
12
44
76
108
13
45
77
109
MELSEC-Q
CH5
CH6
CH7
CH8
136
168
200
232
137
169
201
233
140
172
204
236
141
173
205
237
5 - 6

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sw0d5c-qctu-e

Table of Contents