Appendix A - ADM
Setup Screens
NOTE: It is important to set all settings in the System
screens correctly to ensure optimal system perfor-
mance.
Password
If the password is not "0000", the password must be
entered to access the setup screens.
System 1
External Pump Control: Enable feature that automati-
cally turns on and off the pump when using a handheld
dispense gun with an integrated trigger switch.
Enable Diagnostic Screen: Choose whether to show
the Diagnostic screen.
Enable Temp. Adjustments: Allows temperature ad-
justments on the Heat-A and Heat-B Run screens.
Enable Pump Autostart: Automatically turns the pump
on after reaching setpoint temperature and heat soak is
complete.
Enable Tandem System: Enable all secondary system
ADM screens.
102
Heat Soak: Time for to preheat after all zones have
reached their target temperatures. Pump cannot turn on
until timer is complete. The heat soak is a user-defined
time.
•
Range: 1-120 minutes
•
0 disables heat soak
Pump Inactive Timeout: If no pump movement is
detected or either pump for (x) amount of time, all
heated zones enter setback mode. After an additional
amount of time (x), the heat will turn off.
•
(x) Range: 0-120 minutes
•
0 disables heat soak
System 2
Enter low and high temperatures for an alarm or warning
to occur.