5.6.5.10. Charge Control
Clicking on Charge Control in the submenu screen for Battery Functions
will display the following screen.
Screen 24
System Manager CIP
System Manager CIP
This screen is used to activate or deactivate the charge control function of the
system and to set the applicable charge current limit. This function is used to
prevent overcharging of the battery by limiting the amount of charging
current that can be applied to it by the rectifiers.
If the charge control function is to be used, proceed as follows:
User Manual
Lorain Power System (AP6C55CA/CB)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
• Enter the maximum amount of charging current allowed to go into the
battery as per battery manufacturer's recommendation, and then click
on the
button to confirm the value.
• System Manager CIP Only: Enter a minimum voltage for the rectifier
output during the charge control process, and click on the
to confirm the value.
Configuring and operating the system 97
Standard 10.00 (March 2008)
button
UM6C55C (P7000597)