Emerson Lorain CIP 4890 AP6C55CB User Manual page 86

Lorain cip 4890/48120 lorain cip access 48120 power systems ap6c55ca/cb
Table of Contents

Advertisement

86 Configuring and operating the system
Important parameters need to be entered in the General Battery Test Settings
box of screen 18 for the tests to be valid:
Clicking on Battery Test in the submenu screen for Battery Functions will
display the following screen.
UM6C55C (P7000597)
Standard 10.00 (March 2008)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Note: A battery test cannot be activated if there is an ongoing major or
minor alarm.
The "End Voltage (V)": this is the expected battery voltage at the end
of the programmed test time (discharge duration), for the actual load
current on the system, according to the battery manufacturer's
discharge curve. If the battery capacity is lower and/or the load on
the system higher than expected, this voltage will be reached before
the end of programmed test time and the test will be terminated.
The "Rectifier Voltage During Test (V)": this is the voltage at which
the rectifiers are placed in standby during the test, in order to take
over should the battery voltage lower beyond the "End Voltage (V)"
for any reason (ex.: very bad battery). This value must be lower than
the "End Voltage (V)" value.
The "Test Time (min)": this is the maximum duration of the test in
minutes. It is the expected time period to reach the programmed "End
Voltage (V)", for the actual load current on the system, according to
the battery manufacturer's discharge curve.
The "Battery Capacity Discharge Limit (%)" is the percentage of the
nominal capacity to which the battery should be discharged during
the test. This value is obtained by using the formula % = I x T
where I is the actual load current on the system, T is the discharge
time to 1.75 V pc, and NC is the nominal capacity of the battery. For
example, in screen 18, a load of 50 A was used for a 60 minute test
time on a 100 Ah battery, thus giving 50 x 60 = 30.
The "Nominal Capacity (Ah)" is the capacity of the battery, in
ampere-hour, for the calculated discharge time (ex.: 3 hours or 8
hours), according to the battery manufacturer's specifications.
NC
100
Lorain Power System (AP6C55CA/CB)
User Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lorain cip 48120 ap6c55caLorain cip access 48120

Table of Contents