Emerson Lorain CIP 4890 AP6C55CB User Manual page 90

Lorain cip 4890/48120 lorain cip access 48120 power systems ap6c55ca/cb
Table of Contents

Advertisement

90 Configuring and operating the system
This screen displays the following information:
If a "Bad Battery Alarm" or a "Battery Test Failure" alarm is present, the
field and button. To clear an alarm, click on the
Note: The "Bad Battery" and "Battery Test Failure" alarms must be reset
manually; these will not reset automatically, even if the system returns to
normal operation.
Clicking on the Battery test parameters settings line below the four boxes
in screen 19 will return to screen 18.
5.6.5.8. Voltage Boost
Voltage boost (or equalize) is used to bring the cells of a battery back to full
charge state after a low voltage condition (discharge). The voltage boost
function provides three modes of operation: the Manual Voltage Boost, used
to manually start a voltage boost, Automatic Voltage Boost, used to
automatically perform a voltage boost, and the Cyclic Voltage Boost, used to
perform a voltage boost on a cyclic basis.
Clicking on Voltage Boost in the submenu screen for Battery Functions will
display the following screen.
UM6C55C (P7000597)
Standard 10.00 (March 2008)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
a "Battery Test Information" box showing whether there is an ongoing
(active) battery test or not (inactive), the duration of the test so far and the
remaining time if there is an ongoing battery test, the system voltage and
the battery current,
an "Operate Manual Battery Test" with a "Start" button on which to click
to start a manual battery test,
an "Operate Cyclic Battery Test" box in which an ongoing cyclic battery
test can be interrupted, and showing the cyclic battery test status and the
remaining time before the next cyclic battery test will be activated, and,
a "Clear Battery Test Alarms" box to clear the battery test alarms, if any.
Not active field will be replaced by an Active
Clear alarm
Clear alarm
button.
Lorain Power System (AP6C55CA/CB)
User Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lorain cip 48120 ap6c55caLorain cip access 48120

Table of Contents