3.2.5.4. Battery connection section
For AP5C55BA, AP5C55BB, AP5C55BC, AP5C55BE, AP5C55BG,
AP5C55BH; and AP5C55CA, AP5C55CB, AP5C55CC: The battery
connection section consists of three pairs of positive (+) and negative (–)
connectors, for the connecting of up to three small VRLA battery strings as
illustrated in Figure 3.16. For each pair of connectors, the positive (+)
connector is in the upper position and the negative (–) connector is in the
lower position. Guiding brackets inside the shelf help guide the connectors
and prevent shorting of adjacent connector terminals. A rubber grommet also
helps maintaining the cables well secured in the connectors.
For AP5C55BF: Up to three battery strings can be connected individually
(one per connector), or up to six battery strings can be connected in pairs (two
per connector) when using the optional P7001140 or P7001142 battery cable
assembly (See Figure 3.16 and Figure 3.17).
Figure 3.16 – Battery connection section for AP5C55BA, AP5C55BB,
AP5C55BC, AP5C55BE, AP5C55BG, AP5C55BH; and AP5C55CA, AP5C55CB,
AP5C55CC (see also Figure 3.17 for AP5C55BF)
User Manual
Lorain Power System (AP6C55CA/CB)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Note: Ensure that the battery connectors are inserted properly by applying
sufficient pressure. A battery connector is fully inserted when it is flush
with the guiding bracket and approximately 1/4" passed the edge of the
aperture in the right side of the shelf.