Using More than one
transmitter on the bus
Figure 3-16. Multidrop
connection
The 3300 transmitter can be run in multidrop mode. In the multidrop mode
each transmitter has a unique HART address.
The poll address can be changed by using a HART 275 Communicator or by
using the Rosemount Configuration Tools software.
To change the poll address using a 275 Communicator choose HART
command [1, 4, 5, 2, 1].
To change the poll address using the Rosemount Configuration Tools (RCT)
software do the following:
1. Choose the View>Device Commands option.
or
choose the Device Commands icon from the Project Bar Advanced
section.
2. Open the Details folder.
3. Choose the Set Poll Address option.
4. Set the desired address.