Rosemount 3300 Series
4-4
4 mA point
The 4 mA point should be set above the Lower Dead Zone (see Section 2:
Dead Zones). If the 4 mA point is set to a point within the Dead Zone or below
the probe end, the full range of the analog output is not used.
20 mA point
Make sure that the 20 mA point is below the Upper Null Zone.
The 20 mA point should be set below the Upper Dead Zone (see "Dead
Zones" on page 2-7). If the 20 mA point is set to a point within the Dead Zone
the full range of the analog output is not used.
Probe angle
If the transmitter is not mounted vertically the angle from vertical position must
be given.