Sequence Program Operation - Mitsubishi Electric QS001CPU User Manual

Qscpu series safety programmable controller melsec-qs series
Table of Contents

Advertisement

4
CPU MODULE
No.
Name
1)
Module fixing hook
"ALIVE" LED
2)
(Green)
"TEST" LED
3)
(Yellow)
"RUN" LED
4)
(Green)
"ERR." LED
5)
(Red)
"USER" LED
6)
(Red)
"BAT." LED
7)
(Yellow)
8)
Module loading lever
*2
9)
USB connector
10) RUN/STOP/RESET switch
11) Module fixing screw
12) Module fixing latch
13) Battery
14) Battery connector pin
15) Serial number display
*1
: Turns On during the initial processing (self-diagnostics, etc.) right after the power-on or reset cancel.
*2
: When a cable is to be connected to the USB connector at all times, clamp the cable to prevent a loose connection,
shifting, or disconnection by pulling due to carelessness.
*3
: Operate the RUN/STOP/RESET switch with your fingertips.
Do not use any tool such as a screwdriver because the switch part might be damaged.
Table4.2 Part Names
Hook used to fix the module to the base unit.
*1
On
: Normal
Off
: When the hardware watchdog timer error is detected
("ERR." LED is On.)
Indicates the operating mode of the CPU module.
*1
On
: TEST MODE
Flash : When TEST MODE is switched to SAFETY MODE
The "TEST" LED turns off after reset.
(Flash interval: On 200ms/Off 200ms)
Off
: SAFETY MODE
Indicates the operating status of the CPU module.
On
: During operation in "RUN"
Off
: During stop in "STOP" or when the error which stops the operation is detected
Flash : When parameters/program is written during STOP and the RUN/STOP/RESET
switch is moved from "STOP" to "RUN"
(Flash interval: On 200ms/Off 200ms)
: When the self-diagnostics error that will not stop operation, other than a battery
On
error, is detected
Off
: Normal
Flash : When the self-diagnostics error that will stop operation is detected
(Flash interval: On 200ms/Off 200ms)
When the reset operation is performed
(Flash interval: On 60ms/Off 60ms)
On
: When the annunciator (F) turns ON
Off
: Normal
On
: When a battery error has occurred due to the CPU battery voltage drop
Off
: Normal
Used to load the module to the safety base unit.
Connector used to connect to the USB compatible peripheral devices.
(Connector type B)
Can be connected by the USB dedicated cable.
RUN
: Executes sequence program operation.
STOP
: Stops sequence program operation.
*3
: Performs hardware reset and operation initialization when an operation
RESET
error occurs. (
Screw used to fix a module to the base unit. (M3 screw)
Latch used to fix a module to the base unit.
Backup battery for the power failure compensation function of program memory.
For connection of the battery lead wires (When shipped from the factory, the lead wires
are disconnected from the connector to prevent the battery from discharging.)
Displays the serial number on the rating plate.
Application
*1
*1
*1
Section 4.4)
*1
4
4.2 Part Names
1
2
3
4
5
6
7
8
- 4