12.2.4 When the "ALIVE" LED does not turn on or turns off

This section describes the troubleshooting for when the "ALIVE" LED of the CPU module
does not turn on at power-ON of the programmable controller or when the "ALIVE" LED
turns off during operation.
(1) Flowchart for when the "ALIVE" LED of the CPU module does not turn on at
12
- 7
12.2 Troubleshooting Flowchart
12.2.4 When the "ALIVE" LED does not turn on or turns off
power-ON of the programmable controller.
The "ALIVE" LED does not turn on.
How is the "POWER"
LED of the power supply
module?
On
Is RUN/STOP/RESET
switch of the CPU
module set at RESET
position?
STOP/RUN position
Can the CPU module
communicate with GX
Developer?
Impossible
Replace the power supply module and
check that the "POWER" LED is on.
How is the "ALIVE" LED
of the CPU module?
Off
Hardware failure of the following modules
1) CPU module
2) Base unit
3) Intelligent function module (if mounted)
Execute operation check sequentially from
the minimum system.
For the module that does not operate, please
consult your local Mitsubishi representative,
explaining a detailed description of the
problem.
Off
Check the wiring and turn on all power
supplies.
RESET position
Set the RUN/STOP/RESET switch to the
STOP position. If it is impossible to set it at
STOP position, failure of the CPU module is
suspected.
Please consult your local Mitsubishi
representative, explaining a detailed
description of the problem.
Possible
Execute PLC diagnostics and
troubleshooting according to its result.
On
Hardware failure of the power supply module
before replacement is suspected.