TROUBLESHOOTING
Error code
Error item
(Hexadecimal)
4060
H
Online
4061
H
registration
error
4063
H
4068
H
406A
H
Circuit inquiry
4070
H
error
4080
H
4081
H
4082
H
Other errors
4083
H
4089
H
12.5 Error codes returned to request source during communication with CPU module
Table12.10 Error code (Continue)
Error details
The online debug function is being executed
by the other peripheral device.
Communication of the online debug function
was unsuccessful.
The registered number of locked files
exceeded the maximum value.
Operation is disabled since the same
operation is being executed from the other
peripheral device.
The drive (memory) number that cannot be
handled (other than 0 to 4) was specified.
The program not yet corrected and the one
corrected by online program change are
different.
Request data error
The sort subject cannot be detected.
The specified command is executing and
therefore cannot be executed.
An attempt was made to perform operation for
the program not registered to the parameters.
An attempt was made to insert/delete the END
instruction by online program change.
Corrective action
• Execute the function again after the operation of the
other peripheral device has ended.
• When the operation was suspended by the other
peripheral device, execute the function again after
executing it on the other peripheral device to normally
complete the operation.
• Execute communication after the registering the online
debug function (e.g. online program change/trace/
conditional monitor).
• Execute again after checking the communication route
such as the communication cable.
Execute again after file access by the other peripheral
device has ended.
Execute again after the operation from the other
peripheral device is over.
Check the specified drive and specify the correct drive.
Execute read from PLC to make the program of the
peripheral device the same as that of the CPU module,
and then execute online program change again.
Check the request data specified in the MC protocol, etc.
Check the data to be searched.
Execute the command again after the request from the
other peripheral device is completed.
Register the program to the parameters.
• Check the specified program file contents.
• Write the program after setting the CPU module to the
STOP status.
9
10
11
12
12
- 70