QA1S6ADP-S1 Q-AnS Base Unit Conversion Adapter User's Manual QA1S6ADP-S1 Thank you for purchasing the Mitsubishi Electric MELSEC-AnS series programmable controllers. Before using this product, please read this manual and relevant manuals carefully to handle the product correctly. MODEL QA1S6ADP-S1-U-E MODEL CODE 13JZ96 IB(NA)-0800539ENG-B(1612)MEE ...
CONDITIONS OF USE FOR THE PRODUCT (1) Mitsubishi programmable controller ("the PRODUCT") shall be used in conditions; i) where any problem, fault or failure occurring in the PRODUCT, if any, shall not lead to any major or serious accident; and ii) where the backup and fail-safe function are systematically or automatically provided outside of the PRODUCT for the case of any problem, fault or failure occurring in the PRODUCT.
CONTENTS CONDITIONS OF USE FOR THE PRODUCT ........1 TERMS .
Page 5
Appendix 1 Marking and Information Disclosure for the Restriction on Use of Hazardous Sub- stances in Electrical and Electronic Products Required by the New China RoHS ............. . 26 REVISIONS .
TERMS Unless otherwise specified, this manual uses the following terms. Term Description A1S5B A generic term for the A1S52B-S1, A1S55B-S1, and A1S58B-S1 extension base units (type requiring no power supply module) where AnS series I/O modules and special function modules can be mounted A1S6B A generic term for the A1S65B-S1 and A1S68B-S1 extension base units (type requiring power supply module) where AnS series I/O modules and...
OVERVIEW About This Manual This manual describes the specifications, configuration devices, part names, settings, and mounting and installation methods of the QA1S6ADP-S1 Q-AnS base unit conversion adapter. For contents that are not described in this manual, such as safety precautions and EMC and Low Voltage Directives, refer to the Safety Guidelines.
Packing List The following items are included in the package of this product. Item Quantity Adapter (QA1S6ADP-S1) Special metal fixture A Special metal fixture B Adapter mounting screw (M36) Special metal fixture mounting screw (M525) Special metal fixture mounting screw (M528) Plain washer (M5) Fixing screw cover This manual...
SYSTEM CONFIGURATION System Configuration Example The following system can be configured using the QA1S6ADP-S1. [Level setting] Extension level setting connector CPU module Main base unit Q38B (Q3 B) Q series extension base unit Q68B (Q5 B/Q6 B) A1S68B-S1 AnS series extension base unit with the QA1S6ADP-S1 (QA1S6ADP-S1+A1S5 B/A1S6 B) A1S68B-S1...
Restrictions This section describes the restrictions when the QA1S6ADP-S1 is used. Applicable CPU modules The following CPU modules support the connection with the QA1S6ADP-S1+A1S5B/ A1S6B. • High Performance model QCPU • Universal model QCPU with a serial number (first five digits) of "13102" or later Base unit connection •...
Configuration Devices Applicable base units The following table lists the extension base units where the QA1S6ADP-S1 can be mounted. Name Model Remarks Extension base unit (type requiring A1S52B-S1, A1S55B-S1, A1S58B-S1 no power supply module) Extension base unit (type requiring A1S65B-S1, A1S68B-S1 power supply module) Mountable modules...
Page 13
Name Model Remarks Intelligent communication module A1SD51S MELSECNET, MELSECNET/B A1SJ71AP23Q, A1SJ71AR23Q, A1SJ71AT23BQ local station data link module Paging interface module A1SD21-S1 Position detection module A1S62LS PC fault detection module A1SS91 Memory card interface module A1SD59J-S2 ID interface module A1SD35ID1, A1SD35ID2 ...
0m. Doing so may cause malfunction. When using the programmable controller under pressure, please consult your local Mitsubishi Electric representative. *2 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within premises.
Performance Specifications This section describes the performance specifications of the QA1S6ADP-S1. Item Specifications Internal current consumption (5VDC) 150mA External dimensions 130mm 62mm 78.5mm Weight 0.28kg Tightening torque range of adapter mounting screw (M3) 0.36 to 0.48Nm Tightening torque range of special metal fixture mounting screw (M5) 1.59 to 2.16Nm...
PART NAMES AND SETTINGS Part Names This section describes the part names of the QA1S6ADP-S1. No. Name Application Extension cable connector A connector for sending/receiving signals to/from the main base unit or another extension base unit. An extension cable is connected here. Extension level setting A connector for setting the level of the extension base unit connector...
Extension Level Setting The extension level must be set to both the QA1S6ADP-S1 and the extension base unit. Set the same level to the extension level setting connectors of the QA1S6ADP-S1 and the extension base unit. Caution • Set the extension level setting connectors correctly. If the different levels are set to the QA1S6ADP-S1 and the extension base unit, more than one level is set, the levels overlap, or no level is set, incorrect input or output is generated.
MOUNTING AND INSTALLATION Mounting/Removing the QA1S6ADP-S1 Precautions • Ground the FG terminal of the programmable controller with a ground resistance of 100 or less. • When the QA1S6ADP-S1 is mounted on the A1S5B, the ground cable connected to the FG terminal of the A1S5B must be the one with its core wire size 2...
Page 19
• Installed using a DIN rail Special metal Special metal fixture Mount the special metal fixture A, special fixture A mounting screw (M5×25) metal fixture B, and ground cable as shown Special metal Special metal on the left. fixture B fixture mounting screw (M5×28) Plain washer...
Connect the ground cable to the FG terminal of the A1S5B (when the A1S5B is used). Mount the QA1S6ADP-S1. • Insert the connector of the QA1S6ADP-S1 QA1S6ADP-S1 to the extension cable connector (IN side) Adapter mounting of the extension base unit, and fix the screw (M3×6) adapter with the adapter mounting screws (three locations).
Connecting/Disconnecting Extension Cables Precautions • When laying extension cables, maintain the minimum bending radius of 55mm or more. Failure to do so may cause malfunction due to characteristic deterioration or cable disconnection. • Keep the overall cable distance of extension cables within 13.2m. •...
Connecting procedure Remove the seal over the extension cable connector (IN side) of the QA1S6ADP-S1. Extension base unit QA1S6ADP-S1 Sticker Remove the thin-walled part of the extension cable connector (OUT side) of the QA1S6ADP-S1 using a tool such as a flathead screwdriver (5.575, 6100). Extension base unit Cuts on the thin-walled part...
Hold the connector part of the cable, and insert it to the connector of the QA1S6ADP-S1. Extension base unit QA1S6ADP-S1 Connector Extension cable Fix the cable with the fixing screws (tightening torque: 0.20Nm). Extension base unit Flathead screwdriver QA1S6ADP-S1 Fixing screw When connecting the QA1S6ADP-S1 to the upper level extension base unit with an extension cable, connect the IN side connector of the QA1S6ADP-S1 and the OUT side connector of the upper level extension base unit.
PRECAUTIONS FOR USING THE QA1S6ADP-S1 Current Consumption of the QA1S6ADP-S1 Voltage (5VDC) is supplied to the QA1S6ADP-S1 from the power supply module on the main base unit. Select the power supply module considering the current consumption of the QA1S6ADP-S1. The current consumption of the power supply module on the main base unit will be as follows.
Voltage Drops Across the QA1S6ADP-S1 and Extension Cables Voltage (5VDC) is supplied to the QA1S6ADP-S1 from the power supply module on the main base unit. Voltage drops occur across the QA1S6ADP-S1 and extension cables due to their resistance. If the specified voltage (4.75VDC or higher) is not supplied to the QA1S6ADP- S1+A1S5B/A1S6B, incorrect input or output may be generated.
In the system above, the sum of the voltage drops will be as follows. Extension level Voltage drops across the QA1S6ADP-S1 and extension cables 1st level V1S=V1+RAIA=R1(I2+IA3)+RAIA 2nd level V2S=V1+V2+RA(I2+IA)=V1+R2(I2+IA2)+RA(I2+IA) 3rd level V3S=V1+V2+V3+RAIA=V1+V2+R3IA+RAIA Check that the condition (0.15>VnS) is satisfied. To connect the QA1S6ADP-S1+A1S5B to the main base unit, it is recommended to use the shortest extension cable possible so that the voltage drop is minimized.
EXTERNAL DIMENSIONS The external dimensions of the QA1S6ADP-S1 are shown below. 78.5 (Unit: mm) When an extension cable is connected Power supply module Extension cable 93.6 (Unit: mm)
APPENDIX Appendix 1 Marking and Information Disclosure for the Restriction on Use of Hazardous Substances in Electrical and Electronic Products Required by the New China RoHS...
Page 30
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.
Page 32
20 Waterford Office Park, 189 Witkoppen Road, Avenida Adelino Cardana, 293, 21 andar, Fourways, South Africa Bethaville, Barueri SP, Brazil Tel : +27-11-658-8100 Tel : +55-11-4689-3000 Germany MITSUBISHI ELECTRIC EUROPE B.V. German China MITSUBISHI ELECTRIC AUTOMATION (CHINA) Branch LTD. Mitsubishi-Electric-Platz 1, 40882 Ratingen, No.1386 Hongqiao Road, Mitsubishi Electric...