Mitsubishi Electric QS001CPU User Manual page 179

Qscpu series safety programmable controller melsec-qs series
Table of Contents

Advertisement

12
TROUBLESHOOTING
Error code
Error item
(Hexadecimal)
4135
H
4136
H
4139
H
File-related
413A
errors
H
413FH
4151
H
4160
H
Online
registration
4165
error
H
41C1
H
41C4
H
41C5
H
File-related
41C7
H
error
41C8
H
12.5 Error codes returned to request source during communication with CPU module
Table12.10 Error code (Continue)
Error details
The date/time data of the peripheral device
(personal computer) is beyond the range.
The specified file already exists.
The specified file has exceeded the already
existing file range.
The specified file has exceeded the already
existing file size.
Writing the file to the specified drive is
inhibited
An attempt was made to delete the file
protected by the system.
The registered number of forced inputs/
outputs exceeded the maximum value.
The multiple-block online change system file
does not exist.
The format information data of the specified
drive (memory) is abnormal.
Simultaneously accessible files exceeded the
maximum.
The specified file does not exist.
The specified file or drive (memory) does not
exist.
The specified file has exceeded the already
existing file range.
Corrective action
Execute again after checking the clock setting of the
peripheral device (personal computer).
Execute again after checking the specified file name.
Execute again after checking the size of the specified
file.
Execute again after checking the size of the specified
file.
Check the drive to be specified and write the file again.
Do not delete the target file as it cannot be deleted.
Deregister the unused forced inputs/outputs.
Execute again after securing the area that enables
multiple-block online change at the time of PLC memory
format.
The file information data may be corrupted.
After backing up the data in the CPU module, execute
PLC memory format.
Execute again after decreasing file operations.
Execute again after checking the file.
Execute again after checking the file or drive (memory).
Execute again after checking the size of the specified
file.
If the error recurs after re-execution, the file information
data may be corrupted.
After backing up the data in the CPU module, execute
PLC memory format.
9
10
11
12
12
- 72

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents