12
TROUBLESHOOTING
Error code
Error item
(Hexadecimal)
Already started
42AD
in the same
H
starting source
CRC read
42AE
H
disabled
During history
42AF
H
data update
Communica-
42B0
tion error
H
between CPUs
CPU access
password
42B1
H
cannot be
written
ROM marking
information
42B2
H
cannot be
written
Program
memory data
42B3
H
cannot be
written to ROM
Command
execution
42B4
H
results
mismatch
Command that
cannot be
42B5
executed in
H
the specified
transfer target
CPU access
42B6
password
H
damaged
Illegal user
42B7
H
name
Program size
42B8
H
mismatch
12
- 75
12.5 Error codes returned to request source during communication with CPU module
Table12.10 Error code (Continue)
Error details
The online operation started before is in the
continued status due to some reason (e.g.
communication disturbance during execution,
etc.).
Start the online operation forcibly.
An attempt was made to read the CRC value
to the file in which the CRC value is not stored.
The history file read cannot be started since
the history data update is during execution in
the CPU module.
The communication between CPU A and CPU
B failed.
The CPU module may be faulty.
Writing the CPU access password failed.
A write error to flash ROM occurred while
program memory data is written to ROM.
A write error to flash ROM occurred while
program memory data is written to ROM.
The results of executed functions are different
between CPU A and CPU B.
The online operation that can be executed
only without the transfer target specification is
executed to CPU A or CPU B.
The CPU access password stored in the CPU
module is damaged.
Characters other than ASCII characters are
used for the user name.
The program size stored in the program
memory is different from that of the running
program.
Corrective action
Redo the online operation from the beginning.
• Execute PLC memory format.
• Execute PLC memory initialization.
Execute the read again after a while.
Restart the CPU module.
Write the CPU access password again.
If the same error occurs again, it is a CPU hardware
failure. Please consult your local Mitsubishi
representative.
Write program memory data to ROM again.
If the same error occurs again, it is a CPU hardware
failure. Please consult your local Mitsubishi
representative.
Write program memory data to ROM again.
If the same error occurs again, it is a CPU hardware
failure. Please consult your local Mitsubishi
representative.
Execute the function which became an error again.
If the same error occurs again, it is a CPU hardware
failure. Please consult your local Mitsubishi
representative.
Execute the online operation again after switching the
transfer target to "Not specified".
Write the CPU access password again after PLC
memory initialization.
If the same error occurs again, it is a CPU hardware
failure. Please consult your local Mitsubishi
representative.
Check whether the characters other than ASCII
characters (20 to 7E
) are used for the login user name.
H
Restart the CPU module.
If the same error occurs again, it is a CPU hardware
failure. Please consult your local Mitsubishi
representative.