Lower Display
Prompt
RPUNIT
END ST
SG1 RP
SG2 SP
SG2 TI
SG3 RP
SG4 SP
SG4 TI
4/00
Upper Display
Range of Setting
or Selection
TIME [factory setting]
EU-M
EU-H
DIS
[factory setting]
HOLD
0 to 99 hours:0 to 59 min
(if RPUNIT = TIME)
or
0 to 999 degrees per minute
or hour (if RPUNIT = EU-M
or EU-H)
[factory setting=0.00]
range depends on setpoint
limits [factory setting=0]
0 to 99 hours:0 to 59 min
[factory setting=0]
0 to 99 hours:0 to 59 min
(if RPUNIT = TIME)
or
0 to 999 degrees per minute
or hour (if RPUNIT = EU-M
or EU-H)
[factory setting=0.00]
range depends on setpoint
limits [factory setting 0]
0 to 99 hours:0 to 59 min
[factory setting=0]
DR4300 Circular Chart Recorder Product Manual
Appendix C - Setpoint Ramp/Soak
Parameter
Definition
RAMP UNITS—The selection you make here will
determine whether the ramp segments will be configured
in terms of time or in terms of rate.
TIME—Ramps will be configured in hrs:min.
Engineering Units per Minute—Ramps will be
configured as a rate in EU-M.
Engineering Units per Hour—Ramps will be configured
as a rate in EU-H.
END STATE—Specify whether the program will be
disabled after execution, or be placed in Hold.
SEGMENT 1 RAMP VALUE—Enter the ramp time or
ramp value for Segment 1.
Whether ramp segments are configured in terms of
time or rate depends on whether RPUNIT is set to
TIME or EU-M/EU-H.
SEGMENT 2 SETPOINT—Enter the setpoint for
Segment 2.
SEGMENT 2 TIME—Enter the duration for Segment 2
SEGMENT 3 RAMP VALUE—Enter the ramp time or
ramp value for Segment 3.
SEGMENT 4 SETPOINT—Enter the setpoint for
Segment 4.
SEGMENT 4 TIME—Enter the duration for Segment 4
Programming and Operation