Honeywell DR4300 Product Manual page 105

Circular chart recorder
Hide thumbs Also See for DR4300:
Table of Contents

Advertisement

Lower Display
Prompt
RSTABL
CUTOFF
*Digital input card must be installed.
4/00
Upper Display
Range of Setting
or Selection
NO [factory setting]
KEY
REM1*
REM2*
0 % to 100 %
DR4300 Circular Chart Recorder Product Manual
Configuration, Startup, and Operation
TOTALIZER RESETABLE—This parameter is used to
specify whether and how the totalizer value can be reset.
NO—Totalizer value cannot be reset.
KEY—Totalizer can be reset from the keypad by setting the
"RESET" parameter to "YES".
REM1—Totalizer will be reset when remote (external) switch
(digital input 1) goes to ON (contact closure). This totalizer
reset is independent of any set up of "REMSW1" in the
remote switch set up group.
REM2—Totalizer will be reset when remote (external) switch
(digital input 2) goes to ON (contact closure). This totalizer
reset is independent of any set up of "REMSW2" in the
remote switch set up group.
LOW CUTOFF VALUE—Input % of range below which the
totalizer stops accumulating.
of Recorder with Display
Parameter
Definition
93