D.3 Using Accutune with Duplex (Heat/Cool) Control
Introduction
"TUNE" can be done for applications using Duplex (Heat/Cool) control.
During tuning, Accutune II assumes SP 1 will cause a Heating demand, and then the calculated tuning
parameters will be automatically entered as the first set of PID constants. Likewise, it assumes tuning at
Local SP 2 will cause a Cooling demand, and the cooling parameters will be entered as the second set of
PID constants.
Procedure
After "TUNE" has been enabled in the tuning set up group as described in Section 4, use the procedure in
Table D-2 to start tuning. Note that control group parameter "NumSPs" must be set to "TWO" to enable
the second setpoint.
To abort tuning in progress, press the MAN/AUTO/RESET key to take the recorder out of Auto mode. The
message "AbRT" (abort) will be displayed as the value of tuning set up group parameter "AT ERR". The
tuning parameters will retain the values they had at the start of the Accutune operation.
Step
Heating Tuning
1
2
3
4
5
4/00

Table D-2 Procedure for Using Accutune for Duplex Control

Press
Lower Display
DISP
until you see
Until the value of Setpoint 1 is at the desired value within the Heat
zone.
or
Make sure the recorder is in Auto mode. ("A" indicator lit.)
If not, use the MAN/AUTO/RESET key to put the unit in Auto.
Lower Display
DISP
it is not "USESP1", use
until you see
Lower Display
DISP
until you see
to toggle to
Lower Display
or
DR4300 Circular Chart Recorder Product Manual
Action/Result
Display Setpoint 1.
SP nnn
UseSPn
This is the prompt used to select the setpoint. If
or
TuneOF
If "TuneOF" (tune off) does not appear, then
Accutune is not enabled.
TuneON
Tuning will begin and the lower display will flash
"TUNING". The output will cycle between 50 %
and 100 % (or high output limit). When tuning
has been completed the lower display will again
show "TuneOF". The Heat tuning parameters are
entered for the first set of PID constants in the
tuning set up group.
Appendix D - Using Accutune II
to switch to "USESP1".
229