DR4300 Circular Chart Recorder
Lower Display
Prompt
RATE T
I MIN
or
I RPM
MANRST
102
Upper Display
Range of Setting
or Selection
0.08 to 10.00 minutes
0.08 or less = OFF
[factory setting = 0.0]
0.02 to 50.00
[factory setting = 0.02]
–100 to +100 (in % output)
[factory setting = 0]
DR4300 Circular Chart Recorder Product Manual
Parameter
Definition
RATE—Rate action affects the recorder's output
whenever the deviation between setpoint and process
variable is changing. It affects it more when the
deviation is changing faster. (This is the "derivative"
component of control.)
ATTENTION
If control group parameter "OUTALG"
is "RLYD" (relay duplex), "Tcur" (time/current duplex), or
"CurT" (current/time duplex), and you are using the
recorder in a heat/cool application, RATE T is used for
heat control. Cooling control would use RATE2T
described later in this table.
RESET IN MINUTES PER REPEAT or RESET IN
REPEATS PER MINUTE—Which of these prompts is
displayed depends on the selection made for control
group parameter "MINRPM".
Reset adjusts the recorder's output taking into
consideration both the size of the deviation (SP-PV) and
the duration of the deviation. (This is the "integral"
component of control.) The amount of corrective action
depends on the value of PB or GAIN.
The reset value specified here determines how many
times proportional action is repeated per minute
(I RPM) or the length (in minutes) of the reset action (I
MIN). For example, if I MIN = .5, it is the same as if I
RPM = 2. The result is the same; two resets are
performed in every minute.
ATTENTION
If control group parameter "OUTALG"
is "RLYD" (relay duplex), "Tcur" (time/current duplex), or
"CurT" (current/time duplex), and you are using the
recorder in a heat/cool application, I MIN or I RPM is
used for heat control. Cooling control would use I2 MIN
or I2 RPM described later in this table.
MANUAL RESET—This parameter is only applicable if
control group parameter "CTRALG" is "PDMR"
(PD with manual reset). Because a proportional
recorder will not necessarily line out at setpoint, there
will be a deviation (offset) from setpoint. This reset value
can be used to eliminate the offset and lets the PV line
out at setpoint. The controller output is the computed
output plus the value of MANRST.
4/00