Step
8
9
10
11
12
4/00
Press
To set tip of pen 1 (purple) on zero scale line of chart ± 0.25 % (or quarter
graduation).
or
and you will see:
FUNC
Upper Display
(value)
Lower Display
PEN 100
Wait until pen stops moving upscale.
To set tip of pen 1 (purple) on full scale line of chart ± 0.25 % (or quarter
graduation).
or
to return to normal operation for pen 1.
DISP
you will see:
Upper Display
(value)
Lower Display
INP
If the recorder has 2 pens go to Step 12.
you will see:
FUNC
Upper Display
(value)
Lower Display
INP
Repeat Steps 1, 2, and 8 through 11 for pen 2 (red).
DR4300 Circular Chart Recorder Product Manual
Troubleshooting and Pen Alignment
Action/Result
(approximately 1200 more than the zero value in Step 2)
and the Input 1 indicator will be lit.
and the Input 2 indicator will be lit.
of Recorder with Display
189